Know before you buy
-
Electrician required
Circuit breakers and residual-current devices must be selected and installed by a qualified electrician for the panel, cable and load.
-
Faceplate-confirmed 80A · 30mA · 6kA
AM63LE faceplate: 80A, 230V~ 50/60Hz, IΔn=30mA, Icu=6kA, IEC61009-1, t≤0.1s, Type AC. Selectable leakage Input/Ouit style control per family.
-
Trip curve letter not on faceplate
No B/C (or other) trip-curve letter is visible on the AM63LE faceplate photos. Do not invent a curve — leave unpublished.
Features that make it useful
-
3-in-1 protection
Residual current leakage, overcurrent and short-circuit protection in one DIN-rail RCBO (listing + faceplate IEC61009-1).
-
Separate leakage control switch
Independently enable/disable leakage protection without removing the breaker (listing USP). Follow electrician practice when testing.
-
Fast trip · Type AC
Faceplate t≤0.1s; Type AC residual symbol. IΔn=30mA; Icu=6kA.
-
AM63LE family · 80A face marking
Same model family across amps; ampere rating printed on the face. Related separate listings: 16A, 32A, 63A, 80A.
How to use
-
Have an electrician size the circuit
Confirm load current, cable, and that a 80A / 30mA Type AC RCBO is correct for that branch.
-
Isolate the board and mount on DIN rail
Qualified installer mounts the RCBO, wires L/N line/load correctly, and tests the leakage function monthly with the yellow T button / approved tester.
-
Use leakage switch only with understanding
Leaving leakage protection OFF removes shock-protection benefit—do not treat as a convenience default.
RCBO 80A with Leakage Control Switch
amiciSmart · AM63LE · 80A · 230V~ 50/60Hz · IΔn 30mA · Icu 6kA · Type AC · IEC61009-1 · Separate leakage ON/OFF · DIN-rail
Two-module AM63LE RCBO (80A) for 230V~ panels combining residual-current (leakage), overcurrent and short-circuit protection, with a dedicated switch to enable/disable leakage protection independently. Faceplate: IΔn=30mA, Icu=6kA, t≤0.1...
Orders are processed before 2 PM on dispatch days.
Use code
Use code
Use code
Couldn't load pickup availability
Manuals & videos
Specifications
| SKU | 1x2M-RCBO-MO-80A |
|---|---|
| Product ID | 8768633602203 |
| Brand (handle/face) | amiciSmart |
| Model (faceplate) | AM63LE |
| Rated current In (faceplate) | 80A |
| Rated voltage / frequency (faceplate) | 230V~ 50/60Hz |
| IΔn (faceplate) | 30mA |
| Icu (faceplate) | 6kA |
| Standard (faceplate) | IEC61009-1 |
| Trip time (faceplate) | t≤0.1s |
| Residual type (faceplate) | Type AC |
| Trip curve letter | Not printed on faceplate — unpublished (do not invent) |
| Leakage control | Dedicated separate ON/OFF / selectable leakage Input/Ouit (family) |
| Mounting | DIN-rail · 2-module style |
| Family inventory note (owner) | 80A OOS |
| Marketing claims removed | ‘India’s first’ dropped from guided copy |
| Warranty (listing) | 1 year; support 980-970-9898 / care@amicikart.com |
| Evidence note | Faceplate photos evidence/rcbo-faceplates/ + product.js + owner corrections 2026-09-18 IST |
Frequently asked questions
Is this definitely 80A?
What is the residual current rating?
What trip curve is it (B/C)?
What is the leakage switch for?
Are 16A/32A/63A/80A variants of one Shopify product?
Full Product Description
amiciSmart RCBO AM63LE (80A) with Separate Leakage Control
Draft for product 8768633602203, SKU 1x2M-RCBO-MO-80A. Original title/handle preserved. ‘India’s first’ marketing removed from guided copy.
Evidence: faceplate photos + live product.js + owner corrections 2026-09-18 IST.
Faceplate (AM63LE)
- 80A · 230V~ 50/60Hz · IΔn=30mA · Icu=6kA · IEC61009-1 · t≤0.1s · Type AC
- Trip curve letter: not on faceplate — unpublished
Family
Related separate listings: 16A, 32A, 63A, 80A. Inventory note: 80A OOS.
Qualified electrician required.